
221/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
58
---
BU
Parameter Set damaged
Internal communication (µC1 <> µC2)
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit
59
#
BU
Parameter Set damaged
After initialization, EEPROM page is on
ABORT (last parameterization was pos-
sibly interrupted due to a power failure)
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit.
59
#
BU
Parameter Set damaged
Page number
5A
#
BU
Parameter Set damaged
CRC error of a parameter page
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit
5A
#
BU
Parameter Set damaged
Page number
5B
#
BU
Parameter Set damaged
Page is on ABORT
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit
5B
#
BU
Parameter Set damaged
Page number
5C
#
BU
Parameter Backup Restore
Page is on WR_RESTO
A backup restore was made
Reset the unit.