290/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
19 Addendum 4: LMV52... with O2 trim control and O2 module
13.08.2004
19.13 Technical data
Refer to section 14 Technical data!
Mains voltage «X89-01»
AC 230 V –15 % / +10 %
Safety class
I
with parts according to
II
as per DIN EN 60 730-1
Transformer AGG5.220
-
Primary side
-
Secondary side
AC 230 V
AC 12 V (2x)
Mains frequency
50...60 Hz ±6 %
Power consumption
4 VA
Degree of protection
IP 54, housing closed
Storage
DIN EN 60 721-3-1
Climatic conditions
class 1K3
Mechanical conditions
class 1M2
Temperature range
-20...+60 °C
Humidity
< 95 % r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions
class 2K2
Mechanical conditions
class 2M2
Temperature range
-30...+70 °C
Humidity
< 95 % r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions
class 3K5
Mechanical conditions
class 3M2
Temperature range
-20...+60 °C
Humidity
< 95 % r.h.
Condensation, formation of ice or ingress of water are not permitted!
Basic unit LMV52...
PLL52...
Environmental conditions