230/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
A1
0E
SA
Ramp time too short Air Actuator Actuator operates with too short a ramp
time, or with an angular rotation that is too
long for the ramp time
Recommendation:
1. Match ramp time to the slowest actuator in the system
(SQM48.4/6), OR
2. Reduce the actuator’s angular rotation between special
positions (load stages with multistage operation) based on
angular rotation
= 90° * ramp time / (90° running time of SA)
A1
10
SA
Internal Fault Air Actuator
Timeout during A/D conversion
A1
11
SA
Internal Fault Air Actuator
Fault during ADC test
A1
12
SA
Internal Fault Air Actuator
Fault during A/D conversion
A1
13
SA
Position Fault Air Actuator
Actuator is outside the valid angular rota-
tion (0-90°) or linearization data are faulty
Check to see if actuator is within the valid positioning range
(0-90°)
A1
15
SA
Internal Fault Air Actuator
CAN fault
Check CAN wiring
A1
16
SA
Internal Fault Air Actuator
CRC fault of a parameter page
Check CAN wiring
A1
17
SA
Internal Fault Air Actuator
Page too long open
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit
A1
18
SA
Internal Fault Air Actuator
Page disrupted
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit