16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
AB
38
O2M
Internal Fault O2 Module
Fault during copying of a parameter page Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5... pa-
rameters.
Otherwise, replace defective O2 module
AB
3E
O2M
Internal Fault O2 Module
External plausibility fault.
This type of fault covers possible faults
occurring due to invalid presettings in the
drive commands. In response, the preset-
tings will be ignored
Reset the unit.
! Caution ! If this fault occurred during parameterization:
Check the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5... pa-
rameters.
Otherwise, replace defective O2 module
AB
3F
O2M
Internal Fault O2 Module
Internal plausibility fault.
This type of fault covers possible errors
that cannot practically occur
*2)
B0
#
BU
Fault during test of port outputs
*1)
B0
01
BU
Internal Fault Basic Unit
Fault when resetting the set outputs
B0
02
BU
Internal Fault Basic Unit
Fault during ZR test
B1
01
BU
Internal Fault Basic Unit
Fault during short-circuit test between in-
puts and outputs
*1)
B5
#
BU
O2 monitor
*1)
B5
01
BU
Below O2 Min Value
O2 value has dropped below O2 min.
value
Check setting of the ratio curve.
Increase interval between O2 setpoint and O2 min. value
B5
02
BU
O2 Min Values undefined
Invalid O2 min. value
Define all O2 min. values
B5
03
BU
O2 Setpoints undefined
Invalid O2 setpoint
Define all O2 setpoints
B5
04
BU
O2 Delay Time undefined
Invalid O2 delay time
Adaption at curvepoint 2 or at the highest curvepoint has not
been made. Set these curvepoints
B5
05
BU
Actual O2 Value invalid
No valid actual O2 value in operation for
>= 3 s
O2 module and O2 sensor must be correctly connected.
Mains power supply to the QGO must be connected