16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
A1
19
SA
Internal Fault Air Actuator
Invalid parameter access
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters
Otherwise, replace defective basic unit
A1
1B
SA
Internal Fault Air Actuator
Fault during copying of parameter page
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit
A1
1E
SA
Internal Fault Air Actuator
External plausibility fault. This type of fault
covers possible faults occurring due to in-
valid presettings in the drive commands.
In response, the presettings will be ig-
nored
Check the special positions to see if value range is valid (0-
90°)
A1
1F
SA
Internal Fault Air Actuator
Internal plausibility fault. This type of fault
covers possible faults that can occur due
to strong EMC impact
A2
#
SA
Gas actuator has detected own fault and
reported it to the basic unit.
Type of fault: See diagnostic code
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
A2
See A1
See A1
See A1
See A1
See A1