263/301
Siemens Building Technologies
Basisdokumentation LMV5...
CC1P7550de
HVAC Products
18 Addendum 3: Variable speed drive (VSD) module
21.07.2004
18.5 Description of the connection terminals for the
variable speed drive module
Terminal
designation
Connection symbol
In
put
Out
put
Description Electrical
rating
PIN1
x Power supply for speed sensor
approx. DC 10 V
max. 45 mA
PIN2
x
Speed input
Uin max = DC 10 V
Uin min high level = DC 3 V
Uin max low level = DC 1.5 V
PIN3 x Reference
ground
PIN4
Reserve
X70
FE
Usensor
Pulse-IN
Reserve
2 Wire
3 W ire - PNP
PIN5
x
Functional earth for shield connection
PIN1
x Power supply for fuel meter
approx. DC 10 V
max. 45 mA
PIN2
x
Fuel meter input gas
Uin max = DC 10 V
Uin min high level = DC 3 V
Uin max low level = DC 1.5 V
PIN3
x Reference
ground
X71
Usensor
FE
2 Wire
Pulse-IN
3 W ire - PNP
PIN4
x
Functional earth for shield connection
PIN1
x Power supply for fuel meter
approx. DC 10 V
max. 45 mA
PIN2
x
Fuel meter input oil
Uin max = DC 10 V
Uin min high level = DC 3 V
Uin max low level = DC 1.5 V
PIN3
x Reference
ground
X72
Usensor
FE
2 Wire
Pulse-IN
3 W ire - PNP
PIN4
x
Functional earth for shield connection
PIN1
x Reference
contact
PIN2
x Release
contact
max. AC / DC 24 V
max. 2 A
PIN3
x
Alarm input
DC 0...24 V
PIN4
x 0 / 4...20 mA control of variable speed drive
0...20 mA
RLmax = 750
Ω
PIN5
x Reference
ground
X73
Start - OUT
12-24VDC Alarm-IN
0/4-20mA Setpoint OUT
FE
PIN6
x Functional
earth