27 Parameter list
17.12.2018
Par.
Parameter
Number of Type
Edit
Value range
Increment
Default
Password level
no.
elements
Min.
Max.
setting
Write
Read
Index 1 = prepurge position
Index 2 = postpurge position
1
2
0°
15°
502
No-flame positions air actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16
Edit
0° 90° 0,1°
Index
0
1
2
Value
0°
90°
45°
HF HF
544
Ramp modulating
1
Std_u8
Edit
32 s
80 s
1 s
32 s
HF
HF
545
Lower output limit
undefined = 20 %
1
Output
Edit / clear
20%
100%
0,1%
undefined
HF
HF (GA)
546
Upper output limit
undefined = 100 %
1
Output
Edit / clear
20%
100%
0,1%
undefined
HF
HF (GA)
600
Actuators
601
Selection of reference point
Index 0 = fuel
Index 1 = air
Setting values:
0 = CLOSED (<0°)
1 = OPEN (>90°)
2 Selection
Edit
0
1 1
Index
0
1
Value
1
0
OEM HF
602
Actuator's direction of rotation
Index 0 = fuel
Index 1 = air
Setting values:
0 = counterclockwise
1 = clockwise (exclusively for SQM3)
2 Selection
Edit
0 1 1
Index
0
1
Value
0
0
OEM HF
606
Tolerance limit of position monitoring [0.1°]
Index 0 = fuel
Index 1 = air
Greatest position error where a fault is securely detected
error detection band: (parameter 606-0.6°) to parameter 606
2 Std_u8
edit
0,5° 4° 0,1°
Index
0
1
Value
1,7°
1,7°
OEM HF
611 Type
of
reference
Index 0 = fuel
Index 1 = air
2 Std_u8
Edit
0
3 1
Index
0
1
Value
0
0
OEM HF