165/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
26 Parameter level
17.12.2018
Starting the
warm settings
F
or
A
and
or
P
V
h min s
%
Bi
ld
118
/0
707
Ignition position
P0
can only be set when
symbol
or
is no longer highlighted.
For fuel, keep
F
depressed, for air
A
.
Press
or
to adjust the value.
When symbol
or
is no longer
highlighted, the next curvepoint
P1
can be
selected with
.
F
or
A
and
or
P
V
h min s
%
Bi
ld
123
/0
707
Low-flame position
P1
can only be set when
symbol
or
is no longer highlighted.
The value will be adopted from
P0
.
For fuel, keep
F
depressed, for air
A
.
Press
or
to adjust the value.
When symbol
or
is no longer
highlighted, the next curvepoint
P2
can be
selected with
.
To the next curvepoint
Back to the previous
curvepoint
P
V
h min s
%
Bi
ld
124
/0
707
When changing from
P1
to
P2
for the first time,
curvepoints
P2…P8
will automatically be
calculated and saved.
CALC
appears for a short moment.