190/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
27 Parameter list
17.12.2018
Par.
Parameter
Number of Type
Edit
Value range
Increment
Default
Password level
no.
elements
Min.
Max.
setting
Write
Read
Setting values:
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1)
3 = both
613 Type
of
actuator
Index 0 = fuel
Index 1 = air
Setting values:
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (6 Nm)
2 = 17 s / 90° (10 Nm)
2 Std_u8
Edit
0
2 1 0;
0
OEM
HF
645
Configuration of analog output
0 = DC 0...10 V
1 = DC 2...10 V
2 = DC 0/2...10 V
1 Std_u8
Edit
0
2 1
0 OEM
HF
700
Error history
701
Current error state
701.01 Error
code
25
Std_u8 Read only
0 255 1 0 ---
IS
701.02 Diagnostic
code
25
Std_u8 Read only
0 255 1 0 ---
IS
701.03 Error
class
25
Std_u8 Read only
0 6 1 0
---
IS
701.04 Error
phase
25
Std_u8 Read only
0 255 1 0 ---
IS
701.05 Startup
counter
25
Std_s32 Read only
0 99999999 1
0 --- IS
701.06 Output
25
Output Read only
0% 100%
0,1% 0% ---
IS
702
Latest error in the history
725
Oldest error in the history
900
Process data
903 Current
output
Index 0 = fuel
Index 1 = air
2 Output
Read only
0% 100%
0,1% 0% ---
IS
For query
via
ACS410
922
Incremental position of actuators
Index 0 = fuel
2 Std_s16
Read only
-50° 150°
0,01° 0° ---
IS