13 Fuel meter input X75 pin 1 / X75 pin 2
17.12.2018
13 Fuel meter input X75 pin 1 / X75 pin 2
A fuel meter can be connected to acquire the amount of fuel burnt.
LMV...
Bild 338e/1109
X7
5
Detector supply fuel meter
Fuel meter input
2
1
Figure 71: Fuel meter input X75
13.1 Configuration of fuel meter
13.1.1 Types of fuel meters
The LMV27 is designed for use with fuel meters equipped with a Reed contact. Pulse
frequency at maximum fuel throughput must be below 300 Hz.
13.1.2 Configuration of pulses per volume unit
Depending on the type of fuel meter used, the number of pulses supplied by it per
m³
or
l
fuel must be parameterized. A maximum of 400 pulses per volume unit can be preset.
The correct amount of fuel is acquired only when this parameter is set.
When the parameter is
0
, the fuel meter stops.
No. Parameter
128
Fuel meter: Pulse valency (pulses / volume unit)
13.1.3 Reading and resetting the meter readings
No. Parameter
167
Fuel volume resettable (m³, l, ft³, gal)
The cumulated fuel volume can be read out per parameter. The reading can also be
reset on the parameter level.