The display
shows
Err:
.
The LMV27 initiates safety shutdown.
The display shows current error code
c:
alternating with
diagnostic code
d:
.
Press
/reset
to return to the normal display.
Example: Error code
12
/ diagnostic code
0
P
V
h min s
%
B
ild
2
4
/0
70
7
22.1.4.5. General information
The LMV27 displays an event which does not lead to
shutdown.
The display shows current error code
c:
alternating with
diagnostic code
d:
.
Press
/reset
to return to the display of phases.
Example: Error code
111
/ diagnostic ode
0
Note
For meaning of the error and diagnostic codes, refer to chapter
Error code list
.
When an error has been acknowledged, it can still be read out from the error history.
22.1.4.6. Start prevention
P
V
h min s
%
Bi
ld
196
/0
208
A non-programmed or not completely parameterized
LMV27, or a LMV27 whose operating mode was reset or
changed, displays
OFF UPr
.
22.1.4.7. Safety loop
P
V
h min s
%
Bi
ld
197
/0
208
A LMV27 whose safety loop and / or the burner flange
contact is open, and a load controller ON signal is
present, displays
OFF S
.