39/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
7 Basic unit LMV27
17.12.2018
7.3.6 Gas pressure switch for valve proving X9-04
Input for connection of
Pressure switch valve proving
X9-04. The input is active only
when operating on gas and when valve proving is activated (refer to chapter
Program
sequence
).
No. Parameter
241
Gas: Execution valve proving
0 = no valve proving
1 = valve proving on startup
2 = valve proving on shutdown
3 = valve proving on startup and shutdown
Protective earth (PE)
Pressure switch - valve proving
“L” for pressure switch
LMV...
X9
-0
4
3
2
1
Figure 18: Gas pressure switch valve proving X9-04
Pressure switch valve proving
Input for connection of valve proving with a specific pressure switch. The input is active
only when firing on gas and when valve proving is activated.
Error
code
Diagnostic
code
Meaning for the LMV27
12 81 Fuel
valve
V1
leaking
83 Fuel
valve
V2
leaking
Note
When using configuration
Valve proving via gas pressure switch-min
, it is not possible
to use the input for
Start release gas
.