10 Electronic air-fuel ratio control
17.12.2018
10.2.4 Ignition
The ignition position is approached in phase
Traveling to the ignition position
(38).
The position is set via curve parameterization under
P0
. In modulating operation, this
point is assigned to an output of 10%.
10.2.5 Postpurging
This position is approached in phase
Traveling to postpurging
(72).
The position can be set via the following parameters:
Parameter Actuator
501.02
Postpurge position fuel actuator
502.02
Postpurge position air actuator