113/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
16 Connection to superposed systems
17.12.2018
No. Parameter
141
Operating mode building automation
0 = off
1 = Modbus
2 = reserved
142
Setback time in the event of communication breakdown
Setting values
0 = inactive
1…7200 s
148
Predefined output in the event of communication breakdown with building
automation
Setting values:
For
modulating operation
, the setting range is as follows:
0…19.9 = burner off
20…100 = 20…100% burner output (20 = low-fire position)
For
multistage operation
, use the following settings:
0 = burner OFF
P1...P3 = stage 1...stage 3
Invalid = no output predefined by the building automation system in the event
of communication breakdown
Default setting:
Invalid
The factory settings of the parameters are shown on the
Parameter list
.
Note
For a detailed description of parameter 148, refer to chapter
Default output via building
automation
.
16.2 Modbus
With this type of bus protocol, the LMV27 operates as a slave on the Modbus and the
transmission mode used is RTU (Remote Terminal Unit).
For more detailed information, refer to the Modbus User Documentation (A7541).
No. Parameter
145
Device address for Modbus of LMV27
Setting values
1…247
146
Baud rate for Modbus
0 = 9600
1 = 19200
147
Setting of parity for Modbus communication
0 = none
1 = odd
2 = even
The factory settings of the parameters are shown on the parameter list.
Note
If bus communication breaks down, the mode, Modbus operating mode and predefined
target output must be rewritten.