185/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
27 Parameter list
17.12.2018
Par.
Parameter
Number of Type
Edit
Value range
Increment
Default
Password level
no.
elements
Min.
Max.
setting
Write
Read
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = Ho mod separate circulation control ¹)
24 = Ho 2-stage separate circulation control ¹)
25 = Ho mod. without circulation control ¹)
26 = Ho 2-stage without circulation control ¹)
27 = Ho 3-stage without circulation control ¹)
28 = G mod mech air actuator only ¹)
29 = Gp2 mod mech air actuator only ¹)
¹) Selected operating mode is not released for the LMV27:
With select: Error code 210 diagnostic code 0
205
Function
Load controller contacts staged
0 = standard
1 = stages interchanged
1 Std_u8
Edit
0
1 1
0 OEM
OEM
208 Program
stop
0 = deactivated
1 = prepurge position (phase 24)
2 = ignition position (phase 36)
3 = interval 1 (phase 44)
4 = interval 2 (phase 52)
1
Selection
Edit
0
4
1
0
HF (GA)
HF (GA)
210
Alarm in the event of start prevention
0 = deactivated
1 = activated
1 Selection
Edit
0
1 1
0 HF
HF
211
Fan ramp up time
1
Time
Edit
2 s
60 s
0,2 s
2 s
HF
HF
212
Maximum time down to low-fire
1
Time
Edit
0,2 s
10 min
0,2 s
45 s
HF
HF
213
Waiting time until home run
1
Time
Edit
2 s
60 s
0,2 s
2 s
OEM
OEM
214
Maximum time start release
1
Time
Edit
0,2 s
10 min
0,2 s
25 s
OEM
OEM
215
Repetition limit safety loop
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Recharging time:
Every 24 hours
1 Std_u8
Edit
1
16 1 16 HF
HF
217
Maximum waiting time for detection of detector or pressure
1
Time
Edit
5 s
10 min
0,2 s
30 s
OEM
OEM