202/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
28 Error code list (of all LMV2 / LMV3 types)
17.12.2018
Error
code
Diagnostic code
Meaning for the LMV27
Recommended measures or causes
1. Check the setting of the actuator type (parameter 613.1)
2. Check to see if actuators have been mixed up
3. Check to see if actuator is locked or overloaded
Bit 7
Valency
128
Referencing error due to parameter change
Parameterization of an actuator (e.g. the reference position) has been changed.
To trigger new referencing, this error will be set
86 #
Error
fuel
actuator
0
Position
error
Target position could not be reached within the required tolerance band.
Check to see if the actuator is locked or overloaded.
Bit 0
Valency 1
Line interruption
Line interruption
detected at actuator’s terminals.
Check wiring (voltage X54 across pin 5 or 6 and pin 2 >0.5 V).
Bit 3
Valency
8
Curve too steep in terms of ramp rate
Check position differential between the curvepoints and the modulating operating ramp setting
(parameter 544).
1. Modulating operating ramp 32 seconds
The slope of the curve may be a maximum position change of 31° (15° for SQM33.6 and 9° for
SQM33.7) between 2 curve points in modulating mode.
2. Modulating operating ramp 64 seconds
The slope of the curve may be a maximum position change of 62° (30° for SQM33.6 and 18° for
SQM33.7) between 2 curve points in modulating mode.
Bit 4
Valency
16
Step deviation in comparison with last referencing
Actuator was overloaded or mechanically twisted.
1. Check the setting of the actuator type (parameter 613.0 or 614)
2. Check to see if the actuator is blocked somewhere along its working range.
3. Check to see if the torque is sufficient for the application.
87 #
Error
air
actuator
0
Position
error
Target position could not be reached within the required tolerance band.
Check to see if the actuator is locked or overloaded.
Bit 0
Valency 1
Line interruption
Line interruption detected at actuator’s terminals.
Check wiring (voltage X53 across pin 5 or 6 and pin 2 >0.5 V).
Bit 3
Valency
8
Curve too steep in terms of ramp rate
Check position differential between the curvepoints and the modulating operating ramp setting
(parameter 544).
1. Modulating operating ramp 32 seconds
The slope of the curve may be a maximum position change of 31° (15° for SQM33.6 and 9° for
SQM33.7) between 2 curve points in modulating mode.
2. Modulating operating ramp 64 seconds
The slope of the curve may be a maximum position change of 62° (30° for SQM33.6 and 18° for
SQM33.7) between 2 curve points in modulating mode.
Bit 4
Valency
16
Sectional deviation in comparison with last referencing
Actuator was overloaded or mechanically twisted.
1. Check the setting of the actuator type (parameter 613.1)
2. Check to see if the actuator is blocked somewhere along its working range.
3. Check to see if the torque is sufficient for the application.
90
#
Internal error LMV27