163/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
26 Parameter level
17.12.2018
26.11.4 Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2
mod» and «Lo mod»)
Note
With the
warm settings
, the burner is started up after pressing the
Info
button. Air-fuel ratio
control can now be accurately set while the flame is present. When traveling along the
precalculated curve to high-fire point
P9
,
all intermediate curvepoints (
P2…P8
) must be set.
Automatic operation is released when – after reaching
P9
– the curve settings are quit
by
pressing
ESC
. If the curve settings are aborted earlier (
ESC
or shutdown due to fault), start
prevention
OFF UPr
continues to be active until all points are set.
If required, the gas pressure can be set at the high-fire point. In case the gas pressure is
changed, all points must be checked by traveling along the curve downward and – if required
– must be readjusted.
P
V
h min s
%
Bi
ld
113
/0
707
Identification of start for setting the curve parameters.
/reset
When there is a request for heat.
Note
If, during the time the curve is parameterized, an error occurs which leads to safety
shutdown, parameterization of the curve is quit.
P
V
h min s
%
Bi
ld
114
/0
707
Phase
Standby
(stationary)
P
V
h min s
%
B
ild
1
0
/0
70
7
Phase
Fan ramp up
(fan motor = ON, safety valve = ON)
P
V
h min s
%
Bi
ld
115
/0
707
Phase
Traveling to prepurge
position
P
V
h min s
%
Bi
ld
116
/0
707
Phase
Prepurging
P
V
h min s
%
Bi
ld
117
/0
707
Phase
Traveling to ignition
position