I-T-E Mechanical Interlock (M15404)
31
Support Tie Bar Mounting
A.
With 9-in. long tie bar wrench (8) supplied (Figures 2 and
3) positioned around left pole tie bar connector (9), pull tie
bar connector back in direction of arrow (away from trip
unit) and drop safety wood block (10) with 1-in. dimen-
sion into gap between tie bar connector and trip unit on
right pole. Wood block should come to rest snugly on the
two socket head cap screws as shown in Figure 4.
Remove wrench.
Securing Tie Bar Connector
B.
Two sets of plungers are provided. Select proper length
of plunger (11 ) (Figures 2 and 3) for desired application
and discard the pair of plungers not used. Position
support tie bar assembly from top and insert plunger
through rectangular opening in base from bottom of
base. Tie bar member (12) must fit around tie bar connec-
tor (Figure 3). It may be necessary to gently tap tie bar
member down to achieve snug fit.
Position of Link Assembly
C.
Plunger locator pin (13) (Figure 3) of link assembly should
face toward outer edge of breaker and must engage hole
in plunger Once this engagement is achieved, tighten two
5/16-18 socket head cap screws (14) to 140 in. Ib.
(Figure 2).
NOTE: Plunger is installed only on left hand pole of each circuit
breaker.
Figure 2
Figure 3
Figure 4
Summary of Contents for I-T-E Sensitrip MD Series
Page 2: ......
Page 6: ...4 I T E Sensitrip Digital Circuit Breaker MD and ND Frame Outline Drawings 1 3 Pole ...
Page 8: ...6 MD and ND Frame Trip Adjustments ...
Page 12: ...10 MD and ND Frame Time Current Curve 600 1000A With Short Time Delay Set on Fixed Time ...
Page 13: ...MD and ND Frame Time Current Curve 11 1200A With Short Time Delay Set on Fixed Time ...
Page 14: ...12 MD and ND Frame Time Current Curve 600 100A With Short Time Delay Set on I2 t ...
Page 15: ...MD and ND Frame Time Current Curve 13 1200A With Short Time Delay Set on I2 t ...
Page 16: ...14 MD and ND Frame Time Current Curve 600 100A Without Short Time Settings ...
Page 17: ...MD and ND Frame Time Current Curve 15 1200A Without Short Time Settings ...
Page 18: ...16 MD and ND Frame Time Current Curve Ground Fault Trip Data ...
Page 19: ...MD and ND Frame Time Current Curve 17 Example ...
Page 20: ...18 MD and ND Frame Let Thru Curves ...
Page 31: ...Installation Diagrams 29 ...
Page 35: ...I T E Mechanical Interlock M15404 33 Figure 7 ...
Page 41: ...Installation Diagrams 39 ...
Page 49: ...Installation Diagrams 47 ...
Page 50: ...48 I T E Panelboard Connecting Straps 1 ...
Page 53: ...Installation Diagrams 51 ...