46
I-T-E TELEMAND
®
Electric Motor Operator
F.
With the circuit breaker handle in the OFF position, align
the motor operator mechanism rollers (indicator to be in
OFF position) and the circuit breaker handle by rotating
the lead screw (6) with a screwdriver. The lead screw
access hole is at the bottom of the motor operator (Figure
2).
G.
Close and latch the mechanism cover
H.
Complete the desired control connections and electri-
cally test the motor operator system before reenergizing
the breaker power terminals in accordance with the
electrical operation.
Electrical Characteristics
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AA
AA
AA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AA
AA
AA
Catalog Numbers
Volts AC
Amperes
MOMN6120
MOMN6120L
120
22.7 Amperes In Rush
13.9 Amperes In Running
MOMN6240
MOMN6240L
240
7.2 Amperes In Rush
6.1 Amperes In Running
Electrical Operation
With the breaker and the operating mechanism in the OFF
position, press the ON button to energize the motor The action
will close the breaker. When the breaker handle reaches the
ON position, the motor circuit is disconnected by an internal
limit switch.
With the breaker and the operating mechanism in the ON
position, press the OFF button to energize the motor. The
action will open the breaker. When the breaker handle reaches
the OFF position, the motor circuit is disconnected by an
internal limit switch.
When the circuit breaker trips automatically, there is no
external indication that the breaker has tripped unless a
separate Bell Alarm accessory (contact Siemens for appropri-
ate catalog number) is provided to energize a customer
furnished warning device. After the circuit breaker trips auto-
matically, it is necessary to press the OFF button to move the
breaker handle to the reset position.
Automatic Reset
For automatic reset, an auxiliary switch (contact Siemens for
appropriate catalog number) is used to return the breaker to
the OFF/RESET position after it has been tripped. This auxil-
iary switch is mounted inside the breaker and wired in parallel
with the OFF button. When the breaker trips, the auxiliary
switch closes, energizing the motor circuit which moves the
breaker to the OFF/RESET position.
After the motor operated mechanism has reset the breaker,
the motor operator internal limit switch opens the circuit. To
provide automatic reset, the ON push button must be a single
pole, double throw device and it must be wired per Figure 3.
Manual Operation
Operate the two cover latches and swing the hinged motor
operator cover away from the breaker to expose the breaker
handle. To return to electrical operation, follow the installation
instructions on page 45 deleting Steps B and C. After opera-
tion checks are complete, restore to normal operation.
Allign rollers and handle
Summary of Contents for I-T-E Sensitrip MD Series
Page 2: ......
Page 6: ...4 I T E Sensitrip Digital Circuit Breaker MD and ND Frame Outline Drawings 1 3 Pole ...
Page 8: ...6 MD and ND Frame Trip Adjustments ...
Page 12: ...10 MD and ND Frame Time Current Curve 600 1000A With Short Time Delay Set on Fixed Time ...
Page 13: ...MD and ND Frame Time Current Curve 11 1200A With Short Time Delay Set on Fixed Time ...
Page 14: ...12 MD and ND Frame Time Current Curve 600 100A With Short Time Delay Set on I2 t ...
Page 15: ...MD and ND Frame Time Current Curve 13 1200A With Short Time Delay Set on I2 t ...
Page 16: ...14 MD and ND Frame Time Current Curve 600 100A Without Short Time Settings ...
Page 17: ...MD and ND Frame Time Current Curve 15 1200A Without Short Time Settings ...
Page 18: ...16 MD and ND Frame Time Current Curve Ground Fault Trip Data ...
Page 19: ...MD and ND Frame Time Current Curve 17 Example ...
Page 20: ...18 MD and ND Frame Let Thru Curves ...
Page 31: ...Installation Diagrams 29 ...
Page 35: ...I T E Mechanical Interlock M15404 33 Figure 7 ...
Page 41: ...Installation Diagrams 39 ...
Page 49: ...Installation Diagrams 47 ...
Page 50: ...48 I T E Panelboard Connecting Straps 1 ...
Page 53: ...Installation Diagrams 51 ...