Motor components and options
4.1 Motor components
1FW6 High Speed built-in torque motors
74
Configuration Manual, 01/2020, 6SN1197-0AE03-0BP3
Note
Shutdown time
If Temp-S responds, and its response threshold is not undershot again in the meantime, then
the drive system must shut down (de-energize) the motor within 2 seconds. This prevents
the motor windings from becoming inadmissibly hot.
NOTICE
Motor destroyed as a result of overtemperature
The motor can be destroyed if the motor winding overheats.
•
Connect Temp-S.
•
Evaluate Temp-S.
•
Ensure that the shutdown time is not exceeded.
Note
No temperature monitoring with Temp-S
As a result of their non-linear characteristic, PTC temperature sensors are not suitable for
determining the instantaneous temperature.
Temp-F
The Temp-F temperature monitoring circuit comprises an individual temperature sensor.
Contrary to Temp-S, this temperature sensor only monitors one phase winding. As a
consequence, Temp-F is only used for monitoring the temperature and diagnosing the motor
winding temperature.
NOTICE
Motor destroyed as a result of overtemperature
If you use Temp-F for thermal motor protection, then the motor is not adequately protected
against destruction as a result of overtemperature.
•
Evaluate the Temp-S temperature monitoring circuit to implement thermal motor
protection.
Summary of Contents for 1FW6092-2PC15-6AB3
Page 1: ...1FW6 High Speed built in torque motors ...
Page 2: ......
Page 299: ......
Page 300: ......