Electrical connection
8.1 Permissible line system types
1FW6 High Speed built-in torque motors
242
Configuration Manual, 01/2020, 6SN1197-0AE03-0BP3
8.1
Permissible line system types
Permissible line system types and voltages
The following table shows the permissible line voltages of TN line supply systems for the
motors.
Table 8- 1
Permissible line voltages of TN line supply systems, resulting DC link voltages and
converter output voltages
Permissible line sup-
ply voltage
Resulting DC link voltage U
DC
Converter output voltage (rms value)
U
a max
400 V
600 V (controlled)
528 V (uncontrolled)
425 V (controlled)
380 V (uncontrolled)
480 V
634 V (uncontrolled)
460 V (uncontrolled)
When using the SINAMICS S120 drive system, the motors are always approved for
operation on the following line supplies:
●
TN line systems with grounded neutral point
●
TT line systems with grounded neutral point
●
IT line systems
When operated on IT line systems, a protective device should be provided that switches off
the drive system in the case of a ground fault.
In operation with a grounded external conductor, an isolating transformer with grounded
neutral (secondary side) must be connected between the line supply and the drive system.
This protects the winding insulation from excessive stress.
8.2
Motor circuit diagram
WARNING
Risk of electric shock
If you connect the single-core power cables for phases U V W incompletely or incorrectly,
there is a danger of electric shock.
•
Connect the single-core power cables for phases U V W and the protective earth PE
completely and correctly.