Parameter
Value
Factory setting
Q1 Switch point logic
High-active
Low-active
High-active
Q1 Timer mode
Off
Switch-on delay
Switch-on/off delay
Switch-off delay
Pulse (one shot)
Off
Q1 Timer setup
1 ms ... 30,000 ms
1 ms
Q1 Hysteresis
0 mm ... 2,147.48 mm
OD2000-
030
: 0.1 mm
OD2000-
050
: 0.2 mm
OD2000-
245
: 0.5 mm
OD2000-
350
: 1 mm
OD2000-
700
: 1.5 mm
7.4.3.3
Window output mode (SP1,SP2:Window)
Set an upper and a lower switching threshold (two switching points). If the measured
distance is inside (normally open contact:
High-active
switching point logic) or outside
(normally closed contact:
Low-active
switching point logic) the switching window, a signal
is output (change of output level).
Minimum
1
Maximum
4
2
1
0
3
Figure 13: Switching window (N/O contact: High-active, PNP)
1
Minimum
2
Switching point near
3
Switching point far
4
Maximum
Minimum
1
Maximum
4
2
1
0
3
Figure 14: Switching window (N/C contact: Low-active, PNP)
1
Minimum
2
Switching point near
3
Switching point far
4
Maximum
Selecting output mode and setting parameters
>
Q1 Output
>
>
Q1 Mode
>
>
Q1 Window (SP1,SP2:Window)
>
>
Q1 Output
>
> Parameter >
> Select option, teach-in or set value >
OPERATION
7
8026231//2021-11-17 | SICK
O P E R A T I N G I N S T R U C T I O N S | OD2000
33