Fault code:
Cause / What to do:
0
System OK
11 - 21
Communication error between PLS and LSI:
Check communication line.
Switch power off and back on again.
32 - 35
Internal error:
Switch power off and back on again.
Replace the LSI, or contact SICK Service.
41
Sensor error:
Switch power off and back on again.
Replace the PLS, or contact SICK Service.
43
Sensor has no default password:
Contact SICK Service to configure the default password.
44
Wrong sensor address:
Check wiring between LSI and sensors.
Reconfigure LSI.
56
Configuration error:
Check wiring between LSI and sensors.
57
Internal error:
Switch power off and back on again.
Replace the LSI, or contact SICK Service.
59
Initialization error on channel 1:
Contact SICK Service.
60
Initialization error on channel 2:
Contact SICK Service.
61, 63
OSSD error:
Check output load.
Switch power off and back on again.
Replace the LSI, or contact SICK Service.
64 - 106
Internal error:
Switch power off and back on again.
Replace the LSI, or contact SICK Service.
10.2 LSI fault table
From this table you can find out what the SICK diagnosis fault
codes mean, and ascertain whether you can rectify the fault
yourself. How to carry out SICK diagnosis is described in
section 9.15.
Note:
If you get a fault code which you are unable to locate in this
table, please contact the SICK Service Department.
10.3 SICK Service / Hotline
If you have any further queries, please contact your local
Sick office.