40
SICK LSI Technical Description - 06/98
This dialog box appears. You now have three options:
You can use the taught-in protective field.
You can edit it as a segmented field.
Or you can check it and then activate it in the LSI.
Reject protective field:
•
Click on Cancel. The taught-in protective field is rejected
and the old field retained.
Edit protective field:
•
Click on Edit. You can then edit the taught-in protective
field like a segmented field and then transmit it to the LSI.
Check protective field:
•
Click on Check:
The taught-in protective field is shown on-screen. The space
contour of the sensor is displayed for comparison purposes.
•
Infringe the protective field intentionally and run over the
contour until you reach all 361 points and all measuring rays.
It is important to do this inwards, in a corridor up to around
70 cm from the edge of the protective field.
The status bar indicates the number of checked points.
As soon as you have checked all points, this dialog box
automatically appears.
If you want to cancel the check beforehand:
•
Deactivate the
Monitoring Area - Teach-In
menu function, or
deactivate the Teach-In Monitoring Area button on the
toolbar.
The same dialog box appears.
•
Click on Yes to transfer the monitoring area into the LSI
and confirm with OK.
The taught-in protective field is now active in the LSI.
Note:
You can also edit the taught-in protective field subsequently and
then transmit it as a segmented protective field to the LSI.