Order tab:
This is where you set the order in which the monitoring cases are
to be activated in succession.
Any order: After the current monitoring case any other
monitoring case can be activated.
Unique order: After the current monitoring case only the
monitoring case you selected from the list at the bottom can
be activated.
Alternative order: After the current monitoring case only one
of the two monitoring cases you selected from the list at the
bottom can be activated.
Note on unique and alternative orders:
In programming the order, make sure only one input changes its
state during switchover.
Example of order:
A
B
1. 0
0
2. 1
0
3. 1
1
4. 0
1
Change inputs and outputs
•
From the menu choose
LSI - Configuration - Edit.
•
Or choose the Edit Configuration button from the toolbar.
•
Select the I/O Definitions tab in the LSI Configuration
dialog box.
•
Check the checkbox to indicate whether you have connected
incremental sensors. You can use incremental sensors when
using the LSI to protect a vehicle (see section 9.7).
•
Check the checkboxes for the inputs and outputs you want
to use.
•
Check the checkbox to indicate whether you want contactor
monitoring on the outputs used.