34
SICK LSI Technical Description - 06/98
Change address
You can define whether the LSI is addressed via a universal
address or a single address.
•
From the menu choose
LSI - Configuration - Edit
.
•
Or choose the Edit Configuration button from the toolbar.
•
Select the Address tab in the LSI Configuration dialog
box.
•
Select whether you want to use a universal or single
address.
Universal address (zero, recommended setting):
If you set Universal address, the stored configuration can
be transferred at a later time to any other LSI.
Single address (between 5 and 126):
If you set Single address you assign the LSI the address
specified here for transferring the configuration. It is then
only possible to reload a configuration at a later time if the
address specified here and the one stored in the LSI match.
This makes sense when you want to ensure that a
configuration saved as a file can only be transmitted to
specific LSI units.
Change application variant
You can also subsequently define the field of application of the
LSI system.
•
From the menu choose
LSI - Configuration - Edit
.
•
Or choose the Edit Configuration button from the toolbar.
•
Select the Variant tab in the LSI Configuration dialog box.
•
Select whether you want to use the LSI for area protection or
vehicle protection (e.g. DTS - Driverless Transport Systems).
•
Select the evaluation you want to use.
Standard:
Standard evaluation.
Pixel suppression:
With this setting objects detected by just one pixel per scan
are ignored. This can be useful in preventing error
shutdowns.