Enter and name monitoring areas:
(In the example three monitoring areas are used, named
according to their size.)
Define monitoring cases: Click on Add and make the
settings you need for your application.
Enter a name for each monitoring case and assign sensors
and monitoring areas as described in section 9.3 for the
entry example.
(In the example five monitoring areas are defined: three for
forward and two for reverse.)
Use speed range: Activate this option and enter the speed
range in which the monitoring case is to be active.
Notes:
To avoid errors, make sure that a monitoring case is defined for
every speed which may occur on the vehicle.
Speeds between -10 cm/s and +10 cm/s are interpreted as 0
cm/s, for technical reasons. You can therefore only enter values
less than -10 cm/s or greater than +10 cm/s. To cover the
range ±10 cm/s, enter speed ranges as follows for example:
For forward:
From -10 cm/s to + 150 cm/s
For reverse:
From -300 cm/s to + 10 cm/s
The negative value is always positioned at the left.
When defining speed ranges, note that a maximum of two
monitoring cases can be active at any one time (simultaneous
monitoring cases).