Electrical installation
Operating mode setting, operating mode 1 to 3:
in “External device monitoring (EDM)” select
“Active
”
check “Reset button active”
in “Reset performed immediately after …” select
“Press and release”
in “Connection of the reset button” select
“at the system plug”
Set scanning range in m to suit the distance between sender/receiver using the list box
set required operating mode as per the following table; you can obtain an additional
operating mode using “Add operating mode”
Operating mode 1:
“MCC-TDC sampling in
protective operation”
Operating mode 2:
“Single break PSDI mode”
Operating mode 3:
“Double break PSDI
mode”
Selection of restart interlock
as a function of the
machine controller:
“External”
, if the restart
interlock is realised via
the existing machine
controller
“Internal”
, if the restart
interlock is realised in the
C4000
Selection of restart interlock
as a function of the machine
controller:
“External”
, if the restart
interlock is realised via the
existing machine controller.
In
Start sequence
you must
select
“Without restart
interlock (only
interruption)”
.
“Internal”
, if the restart
interlock is realised in the
C4000. In
Start sequence
you must select
“Standard
(interruption and reset)”
or
“Alternative (reset and
interruption)”
The following applies to the
PSDI control:
with “Release PSDI control”
you must select
“Limited”
the PSDI time monitoring
must be set to
“active”
(max. 30 sec.)
PSDI window:
select “no
PSDI window”
.
Settings as in operating
mode 2 “single break
PSDI”
Note:
The double break
PSDI mode function is not
possible on replacement
for LVU200/300.