Electrical installation
Designation on
LVS4501600
Terminal no. of the
LVS4501600
Terminal no. of the
LCUR1-411
Function
L
1
19 (at 230 V AC)
23 (at 24 V DC)
Voltage supply
N
2
20 (at 230 V AC)
22 (at 24 V DC)
Voltage supply
PE
PE
21
Earth conductor
Contact NC
11
16
Normally closed
circuit with fuse
Contact NC
9
18
Contact NO
7
12
Normally open
circuit with fuse
Contact NO
22
13
Contact NO
20
14
Normally open
circuit with fuse
Contact NO
24
15
MCC IN
4
11
Machine contact
circuit
MCC OUT
3
10
Machine contact
circuit
Restart interlock
10
2
Implementation via
CDS with C4000
Selector switch
(without restart
interlock)
23
4
Implementation via
CDS with C4000
Selector switch (with
restart interlock
21
3
Implementation via
CDS with C4000
EDM IN
6
8
External device
monitoring (only if
used previously)
EDM OUT
8
9
External device
monitoring (only if
used previously)
RESET
17
6
RESET
19
7