Operating instructions
Chapter
5
LCUR1411
8011281/TF99/2013-02-28
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
27
Electrical installation
Selection 2:
The connections on the logic module 1.2, 1.3 or 3.2, 3.3 (A2) must be
checked and, if necessary, wired to suit the old device to be replaced. The wire link 3.4,
1.4 on the logic module remain the same for all device types. As supplied the link pk(C) is
connected to 1.2 and pk(D) to 1.3.
Note jumper between terminal 8 and 9!
As supplied there is a link between 8 and 9 on the terminal strip to the machine controller.
This link must be fitted. Exception:
If the internal (EDM), external device monitoring is used in the old device to be replaced,
the link between terminal 8 and 9 on terminal strip X2 must be removed. The feedback for
the external device monitoring for the external contactor must be connected to terminals 8
and 9 on terminal strip X2.
WARNING