Operating Instructions – MOVITRAC® LTE-B
37
5
Startup with 87 Hz characteristic curve
Startup
Example:
The following information will be sent to the drive if:
• the binary inputs are configured and wired correctly to enable the drive
• parameter
P-12
is set to 3 to operate the drive via SBus
The process data read back from the drive should be in run condition:
5.4
Startup with 87 Hz characteristic curve
The following parameters have to be set:
• P-01: 87 Hz
• P-07: 400 V
• P-08: Motor current for
∆
operation (see nameplate)
• P-09: 87 Hz
Description
Value
Description
PO1 Control word
0
Fast stop on 2nd deceleration ramp (
P-24
)
1
Coast to stop
2
Ramp to stop on process ramp
P-04
3 – 5
Reserved
6
Ramp up (
P-03
) and run with setpoint speed (PO2)
PO2 Setpoint speed
0x4000
= 16384 = maximum speed, e.g. 50 Hz (
P-01
) clockwise
0x2000
= 8192 = 50% of maximum speed, e.g. 25 Hz clockwise
0xC000
= –16384 = maximum speed, e.g. 50 Hz
(P-01)
counterclockwise
0x0000
= 0 = minimum speed as set in
P-02
Description
Value
Description
PI1
Status word
0x0407
Status = run
Output stage enabled
Drive ready
PO data enabled
PI2
Actual speed
Should be equal to PO2 (setpoint speed)
PI3
Actual current
Depends on speed and load
00
I