54
Operating Instructions – MOVITRAC® LTE-B
9
Output power and current carrying capacity without filter
Technical Data
9.3.2
1-phase system AC 230 V for 3-phase AC 230 V motors
MOVITRAC
®
LTE-B – EMC filter class 0
IP20
1)
Type
MC LTE B...
0004-201-1-
00
0008-201-1-
00
0015-201-1-
00
0015-201-4-
00
0022-201-4-
00
0040-201-4-
00
Part number
08296863
08296871
08296898
08296901
08296928
18250394
IP55/NEMA-
12 housing
without
switch
Type
MC LTE B...
0004-201-1-
10
0008-201-1-
10
0015-201-1-
10
0015-201-4-
10
0022-201-4-
10
0040-201-4-
10
Part number
08297789
08297797
08297800
08297819
08297827
18250408
IP55/NEMA-
12 housing
with switch
Type
MC LTE B...
0004-201-1-
20
0008-201-1-
20
0015-201-1-
20
0015-201-4-
20
0022-201-4-
20
0040-201-4-
20
Part number
08297320
08297339
08297347
08297355
08297363
18250416
INPUT
Line voltage V
line
V
1 × AC 200 – 240 V ± 10%
Line frequency f
line
Hz
50/60 Hz ± 5%
Line fuse
A
10
16
20
32 (35)
2)
40
Nominal input current
A
6.7
12.5
14.8
14.8
22.2
31.7
OUTPUT
Recommended motor
power
kW
0.37
0.75
1.5
1.5
2.2
4
PS
0.5
1
2
2
3
5
Output voltage V
motor
V
3 × 20 – 250 V
Output current
A
2.3
4.3
7
7
10.5
16
Cross section of motor
cable Cu 75C
mm
2
1.5
2.5
AWG
16
18
Max. motor
cable length
Shielded
m
25
100
Unshielded
40
150
GENERAL INFORMATION
Size
Size
1
2
3
Heat loss at nominal output
power
W
11
22
45
45
66
120
Minimum braking resis-
tance value
Ω
-
47
1) Device for America, Asia, and Africa
2) Recommended values for UL compliance