Operating Instructions – MOVITRAC® LTE-B
49
8
P-15 Binary input function selection
Parameters
8.3.2
Keypad mode
When
P-12
= 1 or 2 (keypad mode), the following table applies.
8.3.3
SBus control mode
When
P-12
= 3 or 4 (SBus control mode), the following table applies.
11
N.O. contact
Briefly closed for for-
ward movement
N.C. contact
Briefly opened for st
op
N.O. contact
Briefly closed for back-
ward movement
Speed reference
Close binary inputs 1
and 3 at the same
time to stop the motor
with deceleration
ramp 2 (
P-24
).
12
Open: Stop/
Controller inhibit
Closed: Enable/Start
Closed for start
Closed for activation and
deceleration ramp 2
Open: Analog speed
value reference
Closed: Preset speed 1
Speed reference
–
P-15 Binary input 1
Binary input 2
Binary input 3
Analog input
Comments
P-15
Binary input 1
Binary input 2
Binary input 3
Analog input
Comments
Key 5
Key 6
0, 1,
5,
8-12
Open: Stop/Con-
troller inhibit
Closed:
Enable/Start
Open: No function
Closed: Speed up
Open: No function
Closed: Speed
down
Open (0 V):
Clockwise rota-
tion
Closed:
(10-24 V): Coun-
terclockwise rota-
tion
–
Increase
speed
Reduce
speed
2
Open: Stop/Con-
troller inhibit
Closed:
Enable/Start
Open: No function
Closed: Speed up
Open: No function
Closed: Speed
down
Open (0 V):
Speed reference
keypad
Closed:
(10-24 V): Fixed
setpoint speed 1
–
Increase
speed
Reduce
speed
3
Open: Stop/Con-
troller inhibit
Closed:
Enable/Start
Open: No function
Closed: Speed up
Ext. error input:
Open: Controller
inhibit
Closed: Enable
Open (0 V):
Speed reference
keypad
Closed:
(10-24 V): Motor
stops
Connect exter-
nal PTC tem-
perature
sensor or simi-
lar to binary
input 3.
Increase
speed
Reduce
speed
4
Open: Stop/Con-
troller inhibit
Closed:
Enable/Start
Open: No function
Closed: Speed up
Open: Speed ref-
erence keypad
Closed: Speed ref-
erence analog
input
Speed reference
–
Increase
speed
Reduce
speed
6
Open: Stop/Con-
troller inhibit
Closed:
Enable/Start
Open: Clockwise
rotation
Closed: Counter-
clockwise rotation
External error
input:
Open: Controller
inhibit
Closed: Enable
Open (0 V):
Speed reference
keypad
Closed:
(10-24 V): Fixed
setpoint speed 1
Connect exter-
nal PTC tem-
perature
sensor or simi-
lar to binary
input 3.
Increase
speed
Reduce
speed
7
Open: Stop/Con-
troller inhibit
Closed:
Enable/Start
Open: Stop
Closed: Clock-
wise rotation
DI3: External error
input:
Open: Controller
inhibit
Closed: Enable
Open (0 V):
Speed reference
keypad
Closed:
(10-24 V): Fixed
setpoint speed 1
DI1 and DI2
closed: Motor
stops with
rapid stop
ramp
P-24
.
Increase
speed
Reduce
speed
P-15
Binary input 1
Binary input 2
Binary input 3
Analog input
Comments
0, 1, 2,
4, 5, 8
– 12
Open: Controller
inhibit
Closed: Enable
No effect
No effect
No effect
Binary input 1 must be
closed in order to have the
motor running. Start and
stop command are issued
via the gateway.
P
i
f
kVA
Hz
n
Summary of Contents for MOVITRAC LTE-B series
Page 2: ...SEW EURODRIVE Driving the world...
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......