28
Operating Instructions – MOVITRAC® LTE-B
4
Electrical installation
Installation
4.3.4
Communication socket RJ45
2933413771
[1]
Not connected
[2]
Not connected
[3]
+24 V
[4]
Internal bus
1)
1) The bit format is defined as follows: 1 start bit, 8 data bits, 1 stop bit, no parity
[5]
Internal bus
[6]
0 V
[7]
SBus+
2)
2) P-12 must be set to 3 or 4 for SBus communication
[8]
SBus–
[4]
[5]
[6]
[7]
[8]
[3]
[2]
[1]