20
Operating Instructions – MOVITRAC® LTE-B
4
Mechanical installation
Installation
Dimensions of control cabinet with ventilation openings
Dimensions of control cabinet with forced cooling
4.2.4
Cable glands
Use suitable cable glands to achieve the corresponding IP/NEMA classification. The
matching holes must be drilled for this purpose. Refer to the following table for recom-
mended dimensions.
Power rating
Control cabinet with ventilation openings
A
B
C
D
mm
in
mm
in
mm
in
mm
in
Size 1
115 V
: 0.37 kW, 0.75 kW
230 V
: 0.37 kW, 0.75 kW
300
11.81
250
9.84
200
7.87
50
1.97
Size 1
230 V
: 1.5 kW
400 V
: 0.75 kW, 1.5 kW
400
15.75
300
11.81
250
9.84
75
2.95
Size 2
115 V
: 1.1 kW
230 V
: 1.5 kW
400 V
: 1.5 kW, 2.2 kW
400
15.75
300
11.81
300
11.81
60
2.36
Size 2
230 V
: 2.2 kW
400 V
: 4.0 kW
600
23.62
450
17.72
300
11.81
100
3.94
Size 3
All power ranges
800
31.50
600
23.62
300
11.81
150
5.91
Power rating
Control cabinet with forced cooling
A
B
C
D
Air flow
rate
mm
in
mm
in
mm
in
mm
in
Size 1
115 V
: 0.37 kW, 0.75 kW
230 V
: 0.37 kW, 0.75 kW
300
11.81
200
7.87
150
5.91
50
1.97
> 15 m
3
/h
Size 1
230 V
: 1.5 kW
400 V
: 0.75 kW, 1.5 kW
300
11.81
200
7.87
150
5.91
75
2.95
> 15 m
3
/h
Size 2
115 V
: 1.1 kW
230 V
: 1.5 kW
400 V
: 1.5 kW, 2.2 kW
400
15.75
300
11.81
250
9.84
100
3.94
> 45 m
3
/h
Size 2
230 V
: 2.2 kW
400 V
: 4.0 kW
400
15.75
300
11.81
250
9.84
100
3.94
> 45 m
3
/h
Size 3
All power ranges
600
23.62
400
15.75
250
9.84
150
5.91
> 80 m
3
/h
Dimensions
Size 1
Size 2
Size 3
X
mm
22.3
28.2
28.2
in
0.88
1.11
1.11
PG
PG13.5 / M20
PG16 / M22
PG16 / M22
Y
1)
1) Cable inlets Y and Z are pre-punched
mm
22
22
22
in
0.87
0.87
0.87
PG
PG13.5 / M20
PG13.5 / M20
PG13.5 / M20
Z
mm
17
17
-
in
0.67
0.67
-
PG
PG9 / M16
PG9 / M16
-