Startup for operation via fieldbus
Startup
5.3.1
Permitted cable lengths
The permitted total cable length depends on the baud rate set for the SBus:
• 125 kBaud: 500 m (1640 ft)
• 250 kBaud: 250 m (820 ft)
• 500 kBaud: 100 m (328 ft) (factory setting)
• 1000 kBaud: 25 m (82 ft)
Use only shielded cables.
5.3.2
Monitoring transmitted data
The data transmitted via gateway can be monitored by means of one of the following
options:
• MOVITOOLS
®
MotionStudio via the gateway’s X24 engineering interface or optional
via Ethernet
• The gateway’s web page (e.g. on DFE3x Ethernet gateways)
2933672203
[A]
Bus connection
[B]
Gateway (e.g. DFx / UOH gateway)
[C]
Cable to wire
[D]
Splitter
[E]
Selection cable
[F]
Terminating resistor
A
B
D
D
F
C
E
DFP 21B
RUN
X30
BUS
FAULT
ADDRESS
20
0
1
21
22
23
24
25
26
nc
max. 8
00
I