Standard parameters
Parameters
8
Parameters
8.1
Standard parameters
Parameter Description
Value range
Factory
setting
Explanation
P-01
Max. speed
P-02 to 5 × P-09 (max. 500 Hz)
500 Hz
1)
Upper speed limit in Hz or rpm (see
P-10
)
P-02
Minimum speed
0 –
P-01
(max. 500 Hz)
0 Hz
Lower speed limit in Hz or rpm (see
P-10
)
P-03
Acceleration
ramp(s)
0 – 600 s
5 s
Acceleration ramp time from 0 to 50 Hz (fixed) in
seconds.
P-04
Deceleration
ramp(s)
0 – 600 s
5 s
Deceleration ramp time of 50 Hz (fixed) until
standstill in seconds. When set to 0, the fastest
possible ramp time without error is activated.
P-05
Stop mode
selection
In the event of power failure:
0: Maintaining operation
1: Motor coasts to a halt
2: Rapid stop along
P-24
Normal stop:
0: Stop along ramp
P-04
1: Motor coasts to a halt
2: Stop along ramp
P-04
0
In the event of a power failure, the inverter
attempts to move along the set ramps and then
switches off the output stages. With P-05, the
inverter attempts to maintain operation by reduc-
ing the motor speed and using the load as a gen-
erator.
P-06
Energy saving
function
0
Off
0
Automatically reduces the motor voltage with light
loads, if activated. In this case, the smallest possi-
ble motor voltage is 50% of the nominal voltage.
1
On
P-07
Nominal motor
voltage
0.20 – 250 V
230 V
Rated voltage (nameplate) of the motor in volts.
For low-voltage drives, this value is limited to
250 V. When set to 0, voltage compensation is
disabled.
0.20 – 500 V
400 V
2)
P-08
Nominal motor
current
25 – 100% of the inverter output
current
DR motor
rating
Rated current (nameplate) of the motor in
amperes.
P-09
Nominal motor
frequency
25 – 500 Hz
50 Hz
Nominal frequency (nameplate) of the motor.
P-10
Nominal motor
speed
0 – 30000 rpm
0
When set to a value unequal 0, all speed-related
parameters are displayed in rpm. Activates slip
compensation when the motor speed (nameplate)
is set.
P-11
Additional volt-
age/boost
0 – 20% of the max. output volt-
age. Resolution 0.1%
•
Size 1 max. 20%
•
Size 2 max. 15%
•
Size 3 max. 10%
Depends on
motor power
Increases the output voltage of MOVITRAC
®
at
low speeds by a value that can be set in order to
facilitate the breaking away of "jammed" loads. A
motor with forced cooling fan must be used for
continuous duty at low speeds.
f
2
P-07
U
P-07
2
P-09
P-09
0 %
10 %
20 %
P
i
f
kVA
Hz
n