56
Operating Instructions – MOVITRAC® LTE-B
9
Output power and current carrying capacity without filter
Technical Data
9.3.4
3-phase system AC 400 V for 3-phase AC 400 V motors
Sizes 1 and 2
MOVITRAC
®
LTE-B – EMC filter class 0
IP20
1)
Type
MC LTE B...
0008-503-1-00
0015-503-1-00
0015-503-4-00
0022-503-4-00
0040-503-4-00
Part number
08296995
08297002
08297010
08297029
08297037
IP55/NEMA-12
housing without
switch
Type
MC LTE B...
0008-503-1-10
0015-503-1-10
0015-503-4-10
0022-503-4-10
0040-503-4-10
Part number
08297908
08297916
08297924
08297932
08297940
IP55/NEMA-12
housing with
switch
Type
MC LTE B...
0008-503-1-20
0015-503-1-20
0015-503-4-20
0022-503-4-20
0040-503-4-20
Part number
08297452
08297460
08297479
08297487
08297495
INPUT
Line voltage V
line
V
3 × AC 380 – 480 V ± 10%
Line frequency f
line
Hz
50/60 Hz ± 5%
Line fuse
A
5
10
16 (15)
2)
Nominal input current
A
2.9
5.4
7.6
12.4
OUTPUT
Recommended motor power
kW
0.75
1.5
1.5
2.2
4
PS
1
2
2
3
5
Output voltage V
motor
V
3 × 20 – 480 V
Output current
A
2.2
4.1
4.1
5.8
9.5
Cross section of motor cable
Cu 75C
mm
2
1.5
AWG
16
Max. motor
cable length
Shielded
m
25
50
Unshielded
40
75
GENERAL INFORMATION
Size
Size
1
2
Heat loss at nominal output
power
W
22
45
66
120
Minimum braking resistance
value
Ω
-
100
1) Device for America, Asia, and Africa
2) Recommended values for UL compliance
P
i
f
kVA
Hz
n
Summary of Contents for MOVITRAC LTE-B series
Page 2: ...SEW EURODRIVE Driving the world...
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......