Operating Instructions – MOVITRAC® LTE-B
5
Startup for operation via fieldbus
Startup
5.3
Startup for operation via fieldbus
• Start the drive as described in section "Easy startup" (page 33).
• Set parameter
P-12
to "3" or "4" to control the drive via SBus.
• 3 = control word and speed setpoint via SBus, ramp times as defined in
P-03
/
P-04
.
• 4 = control word, speed setpoint and ramp time via SBus.
• Set
P-14
to "101" (default) to enable access to the advanced menu.
• Set the values in
P-36
as follows:
• For a unique SBus address, make a setting between 1 and 63
• For the SBus baud of the gateway, set to "500 kBaud" (default)
• Define the timeout behavior of the drive when communication is interrupted:
• 0: continue with last data (default)
• t_xxx: trip after a delay of xxx milliseconds, trip-reset required
• r_xxx: ramp to stop after a delay of xxx milliseconds, auto-restart with new
data received
• Connect the drive via SBus to the DFx / UOH gateway according to chapter "RJ45
communication socket".
• Set the DIP switch "AS" on the DFx / UOH gateway from OFF to ON to perform auto
setup for the fieldbus gateway. The LED "H1" on the gateway will flash repeatedly
and then remain off. If the LED "H1" is lit, the gateway or one of the drives on the
SBus is not connected or was not started properly.
• The configuration of the fieldbus communication between DFx / UOH gateway and
bus master is described in the corresponding DFx manual.