Operating Instructions – MOVITRAC® LTE-B
41
7
Error codes
Service and Error Codes
"E-triP"
External error (in conjunction with
binary input 3).
•
External error at binary input 3. NC contact was
opened.
•
Check motor thermistor (if connected).
"SC-trP"
Communication failure error
•
Check communication connection between
inverter and external devices.
•
Make sure each inverter in the network is
assigned a unique address.
"P-LOSS"
Input phase failure error
An input phase failed in an inverter designed for
operation on a three-phase system.
"SPIn-F"
Spin start failed
Spin start function unable to detect motor speed.
"dAtA-F"
Internal memory error
•
Parameter not saved, factor settings restored.
•
Try again. If this problem occurs again, contact
SEW-EURODRIVE Service.
"EE-F"
EEPROM error parameter not
saved, factor settings restored.
EEPROM error parameter not saved, factor settings
restored. If this error occurs again, contact SEW-
EURODRIVE Service.
"4-20 F"
Current at analog input not within
defined range.
•
Make sure the input current is within the range
defined in P-16.
•
Check connection cables.
"SC-FLt"
Internal inverter error
Please consult SEW-EURODRIVE Service.
"FAULtY"
"Prog_ _"
Error message Explanation
Solution