Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
146
System Manual, 09/2009, A5E02316180B-02
SOURCE
The field is available in the case of the actions "LIM.VIOLATION" and
"ENERGY PULSE"
In the case of the action "LIM.VIOLATION":
the field "SOURCE" selects the limit whose status is given at the digital
output.
Range: LIMIT LOGIC, LIMIT 0, LIMIT 1, ... LIMIT 11
Default value: LIMIT LOGIC.
In the case of the action "ENERGY PULSE":
The field "SOURCE" selects the type of cumulated power (active
energy or reactive energy):
kWh IMPORT
kWh EXPORT
kVARh IMPORT
kVARh EXPORT
The reference values at which a pulse or an edge is output are defined
in the fields "UNIT" and "PULSES PER UNIT".
UNIT
The field is available when the action "ENERGY PULSE" is selected.
Value of the cumulated power at which a configurable number of
pulses or edges is output. The number of pulses or edges to be output
is defined in the field "PULSES PER UNIT" or "EDGES PER UNIT".
Range: 1, 10, 100, 1000 kVARh, or kW
Default value: 1
PULSES PER
UNIT
The field is available when the action "ENERGY PULSE" is selected.
Number of pulses to be output per unit. The reference unit is defined in
the "UNIT" field.
Range: 1 to 999
Default value: 1
EDGES PER
UNIT
The field is available when the action "ENERGY PULSE" is selected.
Number of edges to be output per unit. The reference unit is defined in
the "UNIT" field.
Range: 1 to 999
Default value: 1
PULSE LENGTH The field is available when the action "ENERGY PULSE" is selected.
Length of the pulse.
Range: 30 to 500 ms
Default value: 100 ms
The minimum length of the pulse pause corresponds to the pulse
duration specified.