Installation
5.5 Installing the expansion modules
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
75
1P
[
61%[
Figure 5-5
Schematic view of assembling the expansion module
1.
Ensure safe isolation from supply.
2.
Discharge yourself.
3.
Mount the SENTRON PAC Power Monitoring Device.
4.
Connect the current terminals and voltage terminals to the SENTRON PAC.
5.
Always hold the expansion module by the plastic enclosure.
6.
Connect the expansion module to the SENTRON PAC. The guide for correct position of
the guide pins will help you to plug in the expansion module correctly.
7.
Tighten the SN62217-B3x22 screws connecting the expansion module to the
SENTRON PAC with a torque of 0.5 Nm.
See also
Electrostatic sensitive devices (ESD) (Page 273)
Operation planning (Page 63)
Tools (Page 69)
Connecting the PAC RS485 expansion module (Page 96)
Mounting on the switching panel (Page 70)