System Manual, 09/2009, A5E02316180B-02
63
Operation planning
4
4.1
Operation planning
Mounting location
The SENTRON PAC4200 device is intended for installation in permanently installed
switching panels within closed rooms.
WARNING
Only operate the device in a secure location.
Can cause death, serious injury or considerable property damage.
SENTRON PAC should only be operated in a lockable control cabinet or a lockable room.
Ensure only qualified personnel have access to this cabinet or room.
Conductive panels and doors on control cabinets must be grounded. The doors of the control
cabinet must be connected to the control cabinet using a grounding cable.
Mounting position
The device must be installed vertically.
s
r
r
Figure 4-1
Mounting position
The preferred direction of viewing is from below at an angle.