Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
158
System Manual, 09/2009, A5E02316180B-02
RESET
The "RESET" dialog box can be used to reset the device settings to the instantaneous
values or the factory default values. The following groups of values can be reset:
●
Maximum/minimum values
●
Counters
●
Universal counter
●
Factory settings
●
Communication parameters
F4
does not immediately reset a value group but marks the group instead. The
"EXECUTE..." menu entry resets the marked value groups.
NOTICE
Rebooting the device
Resetting the last two value groups "FACTORY DEFAULTS" and "COMMUNICATION
PARAM." causes the device to reboot.
After calling the "EXECUTE" menu entry with F4
, a safety query appears on the
display: "Are you sure you want to execute the selected functions?". Answer this query with
F1 or F4.
●
F1
: Cancels the action. The display returns to display mode. All selected value
groups are deselected.
●
F4
: Resets the selected value groups.
After execution with F4
, the confirmation "SELECTION EXECUTED" appears on the
screen or the device is rebooted.
Confirm the message "SELECTION EXECUTED" with F4
.
CLEAR MIN/MAX VALUES
Resets all minimum and maximum values to
the instantaneous value.
RESET COUNTERS
Resets the following counters to zero (0):
•
Energy counters for active energy,
reactive energy, and apparent energy.
•
Operating hours counter
UNIV.COUNTER RESET
Resets the configurable universal counters
to zero (0).
FACTORY DEFAULTS
Resets all device settings to the default
values. Clears minimum/maximum values
Resets all counters.