Appendix
A.3 MODBUS
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
233
A.3.2
Structure - Digital inputs status and digital outputs status with the function codes
0x01 and 0x02
The following are available via MODBUS:
●
"Digital Inputs Status"
●
"Digital Outputs Status"
Input status and output status of the SENTRON PAC Power Monitoring Device
You can use the function codes 0x05 and 0x0F on the digital outputs in addition to the
function codes 0x01 and 0x02.
Table A- 3
Structure - Digital Inputs Status and Digital Outputs Status
Name
Length
Status
Byte
Bit
Bit mask
Access
Digital Outputs Status
32 bits
DO 0.0
3
0
0x00000001
R
Digital Outputs Status
32 bits
DO 0.1
3
1
0x00000010
R
Digital Inputs Status
32 bits
DI 0.0
3
0
0x00000001
R
Digital Inputs Status
32 bits
DI 0.1
3
1
0x00000010
R
Table A- 4
Structure - Digital inputs status and digital outputs status for an expansion module SENTRON PAC 4DI/2DO
on slot 1
Name
Length
Status
Byte
Bit
Bit mask
Access
Digital outputs status
32 bits
DO 4.0
7
0
0x00000001
R
Digital outputs status
32 bits
DO 4.1
7
1
0x00000010
R
Digital inputs status
32 bits
DI 4.0
7
0
0x00000001
R
Digital inputs status
32 bits
DI 4.1
7
1
0x00000010
R
Digital inputs status
32 bits
DI 4.2
7
2
0x00000100
R
Digital inputs status
32 bits
DI 4.3
7
3
0x00001000
R
Table A- 5
Structure - Digital inputs status and digital outputs status for an expansion module SENTRON PAC 4DI/2DO
on slot 2
Name
Length
Status
Byte
Bit
Bit mask
Access
Digital outputs status
32 bits
DO 8.0
11
0
0x00000001
R
Digital outputs status
32 bits
DO 8.1
11
1
0x00000010
R
Digital inputs status
32 bits
DI 8.0
11
0
0x00000001
R
Digital inputs status
32 bits
DI 8.1
11
1
0x00000010
R
Digital inputs status
32 bits
DI 8.2
11
2
0x00000100
R
Digital inputs status
32 bits
DI 8.3
11
3
0x00001000
R
See also
Measured variables without a time stamp with the function codes 0x03 and 0x04 (Page 225)