Appendix
A.1 Measured variables
SENTRON PAC4200
204
System Manual, 09/2009, A5E02316180B-02
Name
Abbrev.
DE + IEC
Abbrev.
EN + UL
Unit
Dis-
play
LIM
SOURCE
Maximum total active power
P
max
W
max
W
7.1
Maximum value of the total active power in the three-phase system
Minimum total active power
P
min
W
min
W
7.2
Minimum value of the total active power in the three-phase system
Total Reactive Power (VARtot)
Q
tot
VAR
tot
VAR 7.0
ΣVARtot
Root of the total squares of the reactive power of the fundamental and harmonics in the phase
conductors (VARtot) referred to the load counting system
Maximum total reactive power (VARtot)
Q
tot max
VAR
tot max
VAR 7.1
Maximum value of the total reactive power of the fundamental and harmonics in the three-phase
system, measured according to VARtot
Minimum total reactive power (VARtot)
Q
tot min
VAR
tot min
VAR 7.2
Minimum value of the total reactive power of the fundamental and harmonics in the three-phase
system, measured according to VARtot
Total Reactive Power (VAR1)
Q
1
VAR
1
VAR 7.0
ΣVAR1
Root of the total squares of the reactive power of the fundamental in the phase conductors referred to
the load counting system
Maximum total reactive power (VAR1)
Q
1 max
VAR
1 max
VAR 7.1
Maximum value of the total reactive power of the fundamental in the phase conductors referred to the
load counting system
Minimum total reactive power (VAR1)
Q
1 min
VAR
1 min
VAR 7.2
Minimum value of the total reactive power of the fundamental in the phase conductors referred to the
load counting system
Total Reactive Power (VARn)
Q
n
VAR
n
VAR 7.0
ΣVARn
Root of the total squares of the reactive power of the harmonics in the phase conductors referred to
the load counting system
Maximum total reactive power (VARn)
Q
n max
VAR
n max
VAR 7.1
Maximum value of the total reactive power of the harmonics in the three-phase system, measured
according to VARn
Minimum total reactive power (VARn)
Q
n min
VAR
n min
VAR 7.2
Minimum value of the total reactive power of the harmonics in the three-phase system, measured
according to VARn
Cos φ a
Cosφ
L1
Disp. PF
a
–
10.0 COSφ a
Power factor of the fundamental in phase conductor a (inductive or capacitive)
Maximum cos φ a
Cosφ
L1 max
Disp. PF
a max
–
10.1
Maximum value of the power factor of the fundamental in phase conductor a (inductive or capacitive)
Minimum cos φ a
Cosφ
L1 min
Disp. PF
a min
–
10.2
Minimum value of the power factor of the fundamental in phase conductor a (inductive or capacitive)
Cos φ b
Cosφ
L2
Disp. PF
b
–
10.0 COSφ b
Power factor of the fundamental in phase conductor b (inductive or capacitive)
Maximum cos φ b
Cosφ
L2 max
Disp. PF
b max
–
10.1
Maximum value of the power factor of the fundamental in phase conductor b (inductive or capacitive)
Minimum cos φ b
Cosφ
L2 min
Disp. PF
b min
–
10.2
Minimum value of the power factor of the fundamental in phase conductor b (inductive or capacitive)