Description
3.10 Ethernet port
SENTRON PAC4200
48
System Manual, 09/2009, A5E02316180B-02
●
Resetting:
–
The process energy counters and the process operating hours counter
–
The counter for process active energy
–
The counter for process reactive energy
–
The counter for process apparent energy
–
All process energy counters, the process operating hours counter and all pulse
counters
–
A specific pulse counter
A maximum voltage of 30 V can be applied to the digital input. Higher voltages require an
external voltage divider.
Signal input
Either edge or pulse counting.
Data is transferred with the help of weighted pulses or edges, e.g. a parameterizable number
of pulses or edges is transferred per kWh.
The countable unit can be defined separately for each application.
The implementation of the pulse shape corresponds to the IEC 62053-31 standard.
3.10
Ethernet port
SENTRON PAC4200 is equipped with an Ethernet interface. This interface facilitates:
●
Configuration of the device using the SENTRON powerconfig software
●
Communication between the device and the energy management system
●
Device firmware updates