42
|
MAGIQTOUCH & MAGIQCOOL MODELS
BMS M1 INDUSTRIAL CONTROL
The MagIQtouch BMS industrial controller is a
24Vdc (SELV) circuit that offers various inputs
and outputs to achieve different functions of
the cooler as well as status feedback. 1 x
BMS M1 module is required per cooler on the
system.
A dedicated 10Vdc is available from the BMS
M1 when the 24Vdc input is applied that can
be used to active cooler functions.
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER M1
ILL2110-A
NAME
LABEL
FUNCTION
LOW
HIGH
INPUT TYPE
POWER IN 24V
POWER OUT 0V
PWR IN
24V
Power supply to operate Interface.
24Vdc per Master Interface.
-
-
24Vdc
UNIT ON/OFF
ON
Activate Cooler – Cooler will operate
according to other inputs.
Unit off
Unit on
DIGITAL
6 - 32Vdc
OPERATION MODE
COOL
Cool or Vent.
Fan only
mode
Cool mode
DIGITAL
6 - 32Vdc
MANUAL DRAIN
DRAIN
Manual Drain On.
Normal
operation
Force drain
DIGITAL
6 - 32Vdc
EMERGENCY
AUXILIARY INPUT
EMERG
AUX
BMS with Emergency shutdown to take
control in the event of shut eg:. fire.
Disable
operation
Enable
operation
DIGITAL
6 - 32Vdc
FAN SPEED
FAN
SPEED
Set Fan speed from 1 - 10.
0Vdc = Fan
speed 0
10Vdc = Fan
speed 10
ANALOGUE
0 - 10Vdc
BMS M1 INPUTS
NAME
LABEL
FUNCTION
LOW
HIGH
OUTPUT TYPE
POWER OUT 10V
PWR OUT
24Vdc
Option for installer to use 10V.
User can use power supply for
inputs and outputs.
-
-
10Vdc
ERROR STATUS
ERROR
STATUS
LED ON to highlight error found. Contact open -
no error
Contact closed
- error
RELAY CONTACT
ERROR CODE
(LED)
DRAIN STATUS
ERROR
CODE
LED will flash in sequence to the
type of error found.
-
-
FLASHING LED
DRAIN
STATUS
Monitor status of Drain.
Contact open -
drain closed
Contact closed
- drain open
RELAY CONTACT
ACTUAL FAN
SPEED
ACT FAN
SPD
Monitor actual fan speed in
operation.
0Vdc = Fan
speed 0
10Vdc = Fan
speed 10
ANALOGUE
0 - 10Vdc
BMS M1 OUTPUTS
EVAP COOLER
EVAP COOLER
EVAP COOLER
EVAP COOLER
CUSTOMER BMS
100m
max
SIG
GND
ERROR
STATUS
COOL
ACT
FAN
SPEED
SIG
GND
SIG
GND
ON
FAN
SPEED
PWR /
ERROR CODE
SIG
GND
SIG
GND
POWER
IN
12V
POWER
IN
0V
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER MS1
SIG
GND
ERROR
STATUS
COOL
ACT
FAN
SPEED
SIG
GND
SIG
GND
ON
FAN
SPEED
PWR /
ERROR CODE
SIG
GND
SIG
GND
POWER
IN
12V
POWE
R
IN
0V
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER MS1
SIG
GND
ERROR
STATUS
COOL
ACT
FAN
SPEED
SIG
GND
SIG
GND
ON
FAN
SPEED
PWR /
ERROR CODE
SIG
GND
SIG
GND
POWER
IN
12V
POWER
IN
0V
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER MS1
SIG
GND
ERROR
STATUS
COOL
ACT
FAN
SPEED
SIG
GND
SIG
GND
ON
FAN
SPEED
PWR /
ERROR CODE
SIG
GND
SIG
GND
POWER
IN
12V
POWER
IN
0V
BMS INDUSTRIAL CONTROLLER M1
BMS INDUSTRIAL CONTROLLER MS1
100m
max
100m
max
100m
max
ILL2217-A
ILL2217-A