SEELEY INTERNATIONAL
- SERVICE GUIDE
|
39
ILL1834-A
ILL1835-A
4. 30 seconds after water reaches the probes,
the pump starts.
5. From the time the pump starts, the Prewet
function continues for 2 minutes. At the end
of this time, the fan (blower) starts at the
speed indicated on the wall control display.
6. If COOL is turned OFF at controller, the
cooler will not commence Prewet function
again unless the pump has run for less than
2 minutes in the previous 10 minutes of fan
(blower) operation.
The Prewet function is set to occur by
default. However it can be turned off in the
SETTINGS menu.
PREWET FUNCTION
ILL1660-A
ILL1661-A
FOR COOLERS WITH WATER
MANAGEMENT SYSTEM FITTED
The following is a description of the Prewet
function that occurs when COOL is selected
for the first time by the MagIQtouch Controller.
This ensures the pads are wet before the fan
(blower) starts.
1. Drain Valve Closes.
2. 9 seconds after drain valve closes the inlet
solenoid valve energises allowing water to
enter tank.
3. The cooler electronics will now wait up to 8
minutes for water to reach the probes. If the
water level has not reached the probes in
that time then a fault code (02) is initiated
(tri-coloured LED will flash red twice) and the
cooler will shut-down.
When the probes recognise water, the RED
LED (Right Hand LED on the cooler electronics
Box or “SAL” LED on the ICON Control Box)
will start to flash.