Chapter 5
Configuring
the EM13X Series
General Meter Setup
92
EM13x Series SMART MULTIFUNCTION METER
Figure
5-11: General Setup Dialog Box – Pulse/Event Counters
Table 14 lists available counter options.
Table 14: Counter Options
Option
Range
Default
Description
Pulse Input
None,
DI1
DI2
DI3
DI4
DI5
DI6
DI7
---
DI14
None
Links a digital input to the
counter
Multiplier
1-9999
1
The value added to the counter
when a pulse is detected on the
pulse source input
Counter Value
Displays the present counter
contents
You can preset a counter to a required value or clear it without
affecting the counter setup.
To preset or clear a counter:
Click the Online button on the PAS toolbar before accessing the setup
dialog box.
Type in the required value into the
Counter Value
field
Click
Send